Building Air Leakage Test Results In Compliance with European Norm EN13829 EPB lipa BVBA EPB-EAP-veiligheid-EPC publieke-phpp-blower door http://www.epblipa.be - info@epblipa.be Patrick Brants-Lien Van Droogenbroeck Varenbergstraat 33 * 9200 Oudegem T/F (052) 33 55 87 * GSM (0486) 02 81 20 Rek. BIC ARSPBE22 / BE 63 9797 8865 8808 BTW 0832.896.339 VEA nr EP12862 EP12862
Building Details Building Address: Kantoor EPB Lipa Woning Liesbet Van Droogenbroeck Oude Baan 3 bus 1 en 2 9200 Dendermonde Test technician: Patrick Brants Varenbergstraat 33 9200 Dendermonde Test company: EPB Lipa BVBA Elevation: 6 m Height above ground: 11 m Building Volume, V: 730,8 m³ Total envelope area, A T BAT 0 m² Building exposure to wind: Partially protected building Accuracy of measurements: 100% Testing Details Fan Model: Retrotec 2000 Fan SN: FT3000253 Gauge Model: DM-2 Gauge SN: 203247
Depressurize set Date: 2014-03-16 Time: 10h45 to 11h15 Environmental Conditions: Barometric Pressure: 102,1 KPa from Direct measurement. Wind speed: Temperature: 3: Gentle breeze Initial: indoors 20 C outdoors 10 C. Final: indoors 20 C outdoors 11 C. Test Data: 10 bias pressures taken for 10 sec each. 10 induced pressures taken for 20 sec each. Bias, initial [Pa] Induced Pressure [Pa] Bias, final[pa] Door Fan Pressure, [Pa] Total flow, V r [m 3 /h] Corrected flow, V env [m 3 /h] -0,32-15,0-20,0-25,0-30,0-35,0-40,0-45,0-50,0-55,0-60,0-65,0-70,0-2,80 144 182 212 242 275 304 355 386 426 458 481 515 144,0 182,0 212,0 242,0 275,0 304, 0 355,0 386, 0 426,0 458,0 481,0 515,0 138,7 175,3 204,2 233,1 264,9 292,8 342,0 371,8 410,4 441,2 463,4 496,1 Error [%] 4,1% 2,2% -1,6% -3,8% -3,9% -5,0% 0,7% 0,4% 2,4% 2,5% 0,8% 1,6% Bias pressure Averages: initial [Pa] P 01-0,32, P 01- -0,32, P 01+ 0,00 final [Pa] P 01-2,80, P 01- -2,80, P 01+ 0,00
Building Gauge Pressure Building Gauge Pressure vs. Flow
Depressurize Test Results Results Results 95% confidence Uncertainty Correlation, r [%] Intercept, Cenv [m 3 /h.pa n ] Intercept, CL [m 3 /h.pa n ] 99,74 95% confidence limits 16,75 14,45 19,45 16,906 14,60 19,60 Slope, n 0,7978 0,7573 0,8383 Air flow at 50 Pa, V50 [m 3 /h] Air changes at 50 Pa, n50 [/h] Permeability at 50 Pa, v50 [m 3 /h.m 2 ] Specific Leakage at 50 Pa, w50 [m 3 /h.m 2 ] 383,0 374,5 392,5 +/-2,4% 0,5245 0,0001 1,050 +/-100,0% Pressurize set Date: 2014-03-16 Time: 11h20 to 11h45 Environmental Conditions: Barometric Pressure: 102,1 KPa from Direct measurement. Wind speed: Temperature: 3: Gentle breeze Initial: indoors 20 C outdoors 11 C. Final: indoors 20 C outdoors 11 C. Test Data: 10 bias pressures taken for 10 sec each. 10 induced pressures taken for 20 sec each. Bias, -2,89 initial [Pa] Induced 15,0 20,0 25,0 30,0 35,0 40,0 45,0 50,0 55,0 60,0 65,0 70,0 Pressure [Pa] Bias, -2,30 final[pa] Door Fan 145 183 214 280 300 340 363 390 423 453 482 505 pressure, [Pa] Total 145,0 183,0 214,0 280,0 300,0 340,0 363,0 390,0 423,0 453,0 482,0 505,0 flow, V r [m 3 /h] Corrected 146,6 185,1 216,4 283,1 303,4 343,8 367,1 394,4 427,7 458,1 487,4 510,7 flow, V env [m 3 /h] Error [%] -3,1% -1,9% -3,8% 8,7% 2,7% 4,3% 0,9% -0,7% -0,6% -1,0% -1,6% -3,2% Bias pressure Averages: initial [Pa] P 01-2,89, P 01- -2,89, P 01+ 0,00 final [Pa] P 01-2,30, P 01- -2,30, P 01+ 0,00
Building Gauge Pressure Building Gauge Pressure vs. Flow
Pressurize Test Results Results Results 95% confidence Uncertainty Correlation, r [%] Intercept, Cenv [m 3 /h.pa n ] Intercept, CL [m 3 /h.pa n ] 99,61 95% confidence limits 12,10 9,825 14,90 12,102 9,835 14,90 Slope, n 0,8812 0,8259 0,9366 Air flow at 50 Pa, V50 [m 3 /h] Air changes at 50 Pa, n50 [/h] Permeability at 50 Pa, v50 [m 3 /h.m 2 ] Specific Leakage at 50 Pa, w50 [m 3 /h.m 2 ] 380,0 370,5 390,5 +/-2,6% 0,5200 0,0001 1,041 +/-100,0% Combined Test Data Results 95% Confidence Interval Uncertainty Air flow at 50 Pa, V50 [m 3 /h] 381,5 372,5 391,5 +/-2,5% Air changes at 50 Pa, n50 [/h] 0,5225 0,0001 1,045 +/-100,0% Permeability at 50 Pa, v50 [m 3 /h.m 2 ] Specific Leakage at 50 Pa, w50 [m 3 /h.m 2 ] +/-2,5% VOOR AKKOORD, Patrick Brants
Test Notes: Blowerdoortoestel is opgesteld in de inkomdeur gebouw en digitale manometer is opgesteld in de vergaderzaal van het gelijkvloers. Beide D-systemen zijn afgesloten aan de inen uitgang van het gebouw met een ballon, geen CV-ketels en geen recirculatiedampkappen. Test is uitgevoerd conform methode A van de norm, verliesoppervlakte bepaald conform EPB decreet, door EPB-verslaggever EPB Lipa bvba. Voor de plannen waarop de berekening is gemaakt, verwijzen wij ook naar de EPB-studie. De te meten zone omvat de volledige
buitenschil van het gebouw. Alle binnendeuren zijn geopend, met uitzondering van de deuren naar de toiletten. "Bij de luchtdichtheidsmeting werden alle voorschriften in het kader van de EPB-regelgeving zoals beschreven in het "specificatiedocument, versie 1 dd 20.10.2010 gerespecteerd", als ook bijlage 5 dd 17.12.2012 aangaande de bijkomende specificaties aangaande luchtdichtheid zijn gerespecteerd. (zie ww.epbd.be/go/luchtdichtheidsmeting) Het binnenvolume is bepaald conform de norm en conform de regels opgesteld door PHP Opmerking: het gebouw behaalt een uitstekend resultaat. Voorafgaand aan deze meting waren er ook reeds 2 metingen methode B uitgevoerd om te kijken welk resultaat haalbaar kon zijn. Deze test toont aan dat ook zonder slabben aan de ramen een voortreffelijk resultaat kan worden behaald. Bij de rondgang in de woning zijn er nergens noemenswaardige lekken of luchtstromen geconstateerd. Foto s van opstelling: Foto s afsluiten D-systeem:
Foto s DM2A tijdens test: Calibration Certificate Retrotec 2000. Range N K K1 K2 K3 K4 Open(22) 0,5214 519,618-0,07 0,8-0,115 1 A 0,503 264,996-0,075 1 0 1 B 0,5 174,8824 0 0,3 0 1 C8 0,5 78,5-0,02 0,5 0,016 1 C6 0,505 61,3 0,054 0,5 0,004 1 C4 0,5077 42 0,009 0,5 0,0009 1 C2 0,52 22 0,11 0,5-0,001 1 C1 0,541 11,9239 0,13 0,4-0,0014 1 L4 0,48 4,0995 0,003 1 0,0004 1 L2 0,502 2,0678 0 0,5 0,0001 1 L1 0,4925 1,1614 0,1 0,5 0,0001 1