Praktisch vervolg op: Studiedag Explosieveiligheid en PROFIBUS. Leusden Juni 2009
|
|
- Casper de Veen
- 8 jaren geleden
- Aantal bezoeken:
Transcriptie
1 Praktisch vervolg op: Studiedag PROFIBUS Leusd Juni 2009
2 Led van Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met 2
3 Wereldwijde prestie support Wat is e Beschermingsmethodiek DP Ex 25 Regionale PROFIBUS Associations (RPA) wereldwijd 36 Competce Cters (PICC) in 13 land 10 Test Laboratoria (PITL) wereldwijd voor certificering test W- EU Belgium RPA PCC Dmark RPA Finland RPA France RPA PCC Great Britain RPA PCC Germany + Austria RPA PCC, PTL Ireland RPA Italy RPA Netherlands RPA PCC, PTL Norway RPA Swed RPA PCC Switzerland RPA PCC Czech Rep. RPA Poland PCC Russia RPA Slovakia RPA E- EU PA Ex uitwerk met America Brazil RPA USA RPA PCC, PTL S. Africa RPA Australia/ New Zealand RPA China RPA PCC, PTL Japan RPA PCC, PTL Korea RPA S.-E.-Asia RPA PCC Thailand RPA PCC Asia RPA = Regional PROFIBUS Association PICC = PROFIBUS Competce Cter PITL = PROFIBUS Test Laboratory 3
4 Programma Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Wat is Atex Wat is veiligheid Temperatuurklasse/zones/gasgroep Beschermingsmethodiek Ex-n Ex-d, e m Ex-i (titeitmodel) FISCO FNICO noem Codering op instrumtatie plaatjes verzamel) Praktijk: (praktijk: typeplaatje lez) (praktijk: loop calculatie) Wat is e veldbus Invtariser welke beschermingsmethodiek + DP of PA de zaal (eindgebruikers) toepass Zone 2 DP uitlegg op basis van model procesinstallatie (ook bereking praktijk) Zone 1 DP uitlegg op basis van model procesinstallatie (ook bereking praktijk) Wat is Fisco wat is Fnico Zone 2 PA uitlegg op basis van model procesinstallatie (ook bereking praktijk) Zone 1 PA uitlegg op basis van model procesinstallatie (ook bereking mak op basis van Fisco) Welke beschermingsmethodiek hanter verschillde bedrijv in de procesindustrie PROFIBUS explosieveiligheid 4
5 Wat is ATEX? Waarom ATEX? ATEX = ATmosphères EXplosibles Wat is e is feitelijk e veiligheidswetgeving voor de EU. Beschermingsmethodiek DP Ex PA Ex uitwerk met 1988 Piper Alpha: 167 dod stofexplosie gasexplosie PROFIBUS explosieveiligheid 5
6 Wat is veiligheid? Het voorkom van: Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS explosieveiligheid 6
7 Voorwaard voor e explosie Hier geldt de branddriehoek: Wat is e Hoe ontstaan gevaarlijke situaties? Beschermingsmethodiek DP Ex PA Ex uitwerk met Verlad van brandbare stoff PROFIBUS explosieveiligheid 7
8 Voorwaard voor e explosie Brandbare stof moet voldode aanwezig zijn Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Vuistregel: 10 liter brandbare stof in e afgeslot ruimte van ca. 100m 3 vormt reeds e explosiegevaarlijke situatie (6m x 6m x 3m) Realiser we ons de mogelijke gevolg? PROFIBUS explosieveiligheid 8
9 Stappplan voor veiligheid De beveiliging dit te geschied in 3 stapp: Wat is e Beschermingsmethodiek DP Ex 1. Voorkom de vorming van e explosieve atmosfeer 2. Voorkom ontsteking van e explosieve atmosfeer 3. Verklein het effect van e explosie PA Ex uitwerk met PROFIBUS explosieveiligheid 9
10 Resultaat na stofexplosie Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS explosieveiligheid 10
11 Ontstekingsbronn Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Hete oppervlakk Elektrische vonk Mechanische slag wrijving Straling (optisch, elektromagnetisch ioniserd) Vlamm hete gass (exotherme reacties) Adiabatische compressie Blikseminslag Elektrostatische ontlading PROFIBUS explosieveiligheid 11
12 Elektrostatische ontlading Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS explosieveiligheid 12
13 Zone concept Wat is e Beschermingsmethodiek DP Ex Zone 0 Zone 20 Zone 1 Zone 21 Aanwezigheid van explosiegevaarlijke atmosfeer Continue of langdurig of regelmatig Af toe Ge actieve ontstekingsbron bij Normaal bedrijf fout bij één beschermingswijze of bij het optred van 2 onafhankelijke fout Normaal bedrijf met regelmatig optredde storing Certificeringplicht voor elektrische apparat Apparaat categorie volgs 94/9/EC Ja Categorie 1 Ja Categorie 2 PA Ex uitwerk met Zone 2 Zone 22 Niet waarschijnlijk slechts voor e korte periode Normaal bedrijf Nee (leveranciersverklaring) Categorie 3 Zonering is e plicht voor de plant eigaar PROFIBUS explosieveiligheid 13
14 Voorbeeld Zone indeling Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Verladingsstation voor brandbare stoff PROFIBUS explosieveiligheid 14
15 Explosie (materieel) groep Wat is e Explosieveilig elektrisch materiaal is verdeeld in 2 groep Groep I Groep II Beschermingsmethodiek DP Ex PA Ex uitwerk met Elektrische apparatuur Elektrische apparatuur voor mijnbouw voor alle andere gevaarlijke gebied PROFIBUS explosieveiligheid 15
16 Gasgroep Gass damp zijn onderverdeeld in gasgroep Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Gevaar IIC (bijv. Waterstof) IIB (bijv. Ethyle) IIA (bijv. Propaan) I (Methaan) Let op de schrijfwijze in specificaties: Zone IIC is e regelmatig voorkomde fout! PROFIBUS explosieveiligheid 16
17 Temperatuurklass Wat is e Temperatuurklasse van het elektrisch materieel Ontstekingstemperatuur van het brandbare materiaal Hoogst toelaatbare oppervlakte temperatuur Beschermingsmethodiek DP Ex PA Ex uitwerk met T1 > 450 C 450 C T2 > 300 C 450 C 300 C T3 > 200 C 300 C 200 C T4 > 135 C 200 C 135 C T5 > 100 C 135 C 100 C T6 > 85 C 100 C 85 C PROFIBUS explosieveiligheid 17
18 Materieelgroep / temperatuurklasse T1 T2 T3 T4 T5 T6 Wat is e I II A Methaan Aceton Butaan Petroleum Acetaldehyde Beschermingsmethodiek Ammoniak Azijnzuur Bze Ethaan Ethylacetaat N-butylalcohol Dieselolie Kerosine Stookolie Hexaan Bzine DP Ex Methanol Propaan Styre PA Ex Tolue uitwerk met II B Stekoolgas Ethyle Zwavelwaterstof Ethylether Koolmonoxide Propyleoxide II C Waterstof Acetyle Zwavelkoolstof *) 102 C T6 Ethylnitraat PROFIBUS explosieveiligheid 18
19 Ontsteekergie & ontsteektemperatuur Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Verschillde begripp maar beide belangrijk! Voorbeeld: waterstof, IIC, T1 Ontsteektemperatuur: 585 C Min. Ontsteekergie: 20 µjoule acetaldehyde, IIA, T4 Ontsteektemperatuur: 140 C Min. Ontsteekergie: 370 µjoule PROFIBUS explosieveiligheid 19
20 Beschermingsmethodiek (BTO s) Wat is e Beschermingsmethodiek Ex d Ex p EN Norm Drukvast omhulsel Pressurized, inwdige overdruk DP Ex PA Ex uitwerk met Ex e Ex ia Ex ib Ex m Ex q Erhöhte Sicherheit, verhoogd veilig Intrinsieke veiligheid voor zone 0, 1 of 2 Intrinsieke veiligheid voor zone 1 of 2 Moulded, ingegot materieel Quartz, poedervulling Ex o Olievulling Ex n Non incdive, niet ontstekd (zone 2!) PROFIBUS explosieveiligheid 20
21 Drukvast omhulsel (Ex d) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Beschermingsmethode om vonkde of heet wordde elektrische onderdel in e gevaarlijke atmosfeer toe te kunn pass Indi binn dit omhulsel e ontploffing optreedt, is dit sterk goeg voor de korte dynamische overdruk zal de overdruk temperatuurverhoging afgebouwd word via de zg. vlamdoofweg (gormeerde (tolerantie) pasvlakk schroefdrad) PROFIBUS explosieveiligheid 21
22 Drukvast omhulsel (Ex d) Wat is e Energie verlies Beschermingsmethodiek DP Ex PA Ex uitwerk met Interne explosie Principe werking van de vlamdoofweg PROFIBUS explosieveiligheid 22
23 Drukvast omhulsel (Ex d) Inkapseling methodes: Wat is e Beschermingsmethodiek 1) Inkapseling van de gehele behuizing Toepassing: Ex d kast voor installatie van convtioneel industrieel materiaal DP Ex PA Ex uitwerk met 2) Inkapseling van het compont Toepassing: Ex d modul voor installatie in Ex e kast PROFIBUS explosieveiligheid 23
24 Verhoogde veiligheid (Ex e) Wat is e Beschermingsmethodiek Beschermingsmethode alle toepasbaar bij normaal niet vonkd materieel. De klemming van de elektrische verbinding is verhoogd veilig, door e trilvaste aansluiting. Mogelijk hogere temperatur zijn vastgelegd in de temperatuurklasse van het materieel. DP Ex PA Ex uitwerk met Vernieuwde strgere eis Afdichting ondergaat verouderingstest Kleminrichting ondergaat e trektest op de ader PROFIBUS explosieveiligheid 24
25 Verhoogde veiligheid (Ex e) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Bescherming teg het losrak van de bedrading Temperatuur beperking Bedrading Luchtweg Kruipweg Bescherming teg het indring van stof water, min. IP54 Bescherming teg elektrostatische lading Slagvastheid van tminste 7 Nm PROFIBUS explosieveiligheid 25
26 Ingiet met gietmassa (Ex m) Wat is e Beschermingsmethodiek DP Ex PA Ex Beschermingsmethode waarbij elektrisch vonkd of heet wordd materieel compleet ingegot wordt in e kunststof hars. weerstand teg div. invloed (veroudering, slagvastheid) niet hygroscopisch holle ruimt slechts beperkt toegestaan dikte van de potting in norm vastgelegd uitwerk met Toepassing: elektronica, magneetspoel voor klepp, etc. PROFIBUS explosieveiligheid 26
27 Intrinsieke veiligheid (Ex i) Wat is e Beschermingsmethodiek Beschermingsmethode waarbij de ergie in stroomkring quadratisch begrsd wordt door spanning- & stroombegrzing E = ½ x C x U² E = ½ x L x I² U begrsd met zerdiode I begrsd met weerstand DP Ex PA Ex uitwerk met Zone 1: Ex ib (1 fout moet de veilige situatie handhav) Zone 0: Ex ia (2 fout moet de veilige situatie handhav) PROFIBUS explosieveiligheid 27
28 Non incdive (Ex n) Wat is e Beschermingsmethode uitsluitd voor zone 2 verevoudigde uitvoering van bestaande beschermingswijz fabrikant neemt hierbij juridisch eig verantwoordelijkheid Beschermingsmethodiek DP Ex PA Ex uitwerk met Subvariant: Ex na (non Arcing) Ex nc (closed construction) Ex nl Ex ic (limited ergy) Ex np Ex pz (pressurization) Ex nr (restricted breathing) evoudige variant van: Ex e Ex d of Ex m Ex ia, Ex ib Ex p (Ex px, Ex py) Hier zi vel door de bom het bos niet meer! PROFIBUS explosieveiligheid 28
29 Intrinsieke veiligheid (Ex i) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Hier wordt onderscheid gemaakt in: het titeit model (EN , voorhe EN 50020) intrinsiek veilige system (EN , voorhe EN 50039) FISCO (& voorhe FNICO) (EN ) FISCO : Fieldbus Intrinsically Safe Concept (voor zone 1) FNICO : Fieldbus Non Incdive Concept (voor zone 2) Waarom FISCO? Bij gebruik van veldbus met vaste elektrische parameters gedefinieerde kabel specificaties is PTB ooit op het idee gekom om de loopbereking te verevoudig, mits gebruik gemaakt van FISCO gecertificeerde compont. PROFIBUS explosieveiligheid 29
30 FISCO de normontwikkeling Wat is e Beschermingsmethodiek DP Ex De IEC omvatte in de eerste editie FISCO & FNICO. Doordat Ex nl in de reeds naar Ex ic in de is verhuisd, is FNICO uit de IEC editie 2 verdw. We sprek dus alle nog van FISCO. Huidige ontwikkeling in normcommissie: PA Ex uitwerk met EN wordt opgehev (!); toekomstig geintegreerd in: EN (product) EN (system) PROFIBUS explosieveiligheid 30
31 Stofexplosieveiligheid Wat is e Door de komst van ATEX is er meer aandacht voor stof. Nieuwe beschermingswijz teg ontsteking vanuit de IEC Beschermingsmethodiek DP Ex PA Ex uitwerk met Ex td Ex pd Ex id Ex md : protection by closure for Dust : pressurization for Dust : intrinsic safe for Dust : moulded for Dust PROFIBUS explosieveiligheid 31
32 Bescherming door behuizing Ex td Ex t Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Door middel van e behuizing met voldode gegarandeerde IP afdichting e stofexplosieveilige situatie creër. > IP5x : voor zone 22 > IP6x : voor zone 21 ( zone 22 bij geleidde stoff) uiteraard mèt e max. oppervlakte temperatuur in T C Markeringsvoorbeeld: IP 65 T80 C Ex td A21 T80 C (CENELEC) (IEC) Ex id Ex md variant lijk sterk op de gas variant, waarbij norm uit de IEC serie nu ook naar IEC integrer PROFIBUS explosieveiligheid 32
33 ATEX in detail ATmosphères EXplosibles Wat is e Richtlijn in kader van EU veiligheidsregelgeving Beschermingsmethodiek DP Ex PA Ex uitwerk met Europese Commissie in Brussel PROFIBUS explosieveiligheid 33
34 Twee ATEX Richtlijn Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met ATEX 95 product richtlijn officieel 94/9/EC verplichting voor fabrikant beoogt het wegnem van handelsbelemmering veiligheid van product valt onder de Warwet ATEX 137 installatie of sociale richtlijn officieel 1999/92/EC verplichting voor werkgever beoogt gezondheidsbescherming veiligheid van werknemers valt onder het ARBO Besluit PROFIBUS explosieveiligheid 34
35 De relatie tuss de ATEX Richtlijn Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met ATEX 137 ATEX 95 Zone (gas) Categorie 0 1G 1 2G 2 3G Zone (stof) Categorie 20 1D 21 2D 22 3D PROFIBUS explosieveiligheid 35
36 ATEX 95 certificeringstraject Categorie 1 of M1 Categorie 2 of M2 Categorie 3 Wat is e elektrische apparat andere apparat Beschermingsmethodiek DP Ex EG-Type onderzoek (III) EG-Type onderzoek (III) PA Ex uitwerk met QS Productie (IV) Productkeuring (V) (*) Overestemming met type (VI) (*) Productie QS borging (VII) Interne fabricage controle gegevs aangemelde instantie Interne fabricage controle CE-Markering door fabrikant of aangemelde instantie (*) PROFIBUS explosieveiligheid 36
37 Dus; eis per categorie (elektrisch) Wat is e Categorie 1: EG Type certificaat èn Production Quality Assessmt Categorie 2: EG Type certificaat èn Production Quality Assessmt Beschermingsmethodiek DP Ex PA Ex uitwerk met Categorie 3: Type certificaat (vrijwillig) èn interne productiecontrole PROFIBUS explosieveiligheid 37
38 Voorbeeld van productmarkering Belangrijke uitgangspunt: Wat is e de Europese richtlijn zijn wetmatig verplicht te vervull Beschermingsmethodiek DP Ex PA Ex uitwerk met norm zijn hulpmiddel om aan te ton dat aan de betreffde richtlijn wordt voldaan PROFIBUS explosieveiligheid 38
39 Categorie 1G Wat is e 0344 II 1G EEx ia IIC T4 Beschermingsmethodiek DP Ex PA Ex Ex zone Niet gevaarlijk gebied uitwerk met 0102 II (1)GD [EEx ia] IIC PROFIBUS explosieveiligheid 39
40 Categorie 2G (zone 1) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met 24VDC PROFIBUS DP 0044 II 2(1)G Ex de [ia] IIC T6 PROFIBUS explosieveiligheid 40
41 Categorie 2G 1G (zone 1 zone 0) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met 24VDC PROFIBUS DP 0044 II 2(1)G Ex de [ia] IIC T6 Zone 1 Zone 0 PROFIBUS explosieveiligheid 41
42 Categorie 3G 2G Wat is e II 3(2)G EEx na [ib] IIC T4 Zone 2 Zone 1 Beschermingsmethodiek DP Ex PA Ex uitwerk met 0102 II 2G EEx ia IIC T6 II 3G EEx nl IIC T4 PROFIBUS explosieveiligheid 42
43 Loop calculatie (titeit model) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met transmitter voeding met safety output parameters : Uo = 28V Lo (IIB) = 14mH Lo (IIC) = 2mH Io = 93mA Co (IIB) = 650nF Co (IIC) = 83nF Po = 650mW transmitter met tity parameters Ui <= 28V Li = 10µH Ii <= 120mA Ci = 1nF Pi <= 0.84W aansluitkabel C = 48nF/km L = 0.75mH/km PROFIBUS explosieveiligheid 43
44 Loop calculatie (titeit model) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met remote I/O met safety output parameters : Uo = 26V Lo (IIB) = 20mH Lo (IIC) = 5.3mH Io = 84.3mA Co (IIB) = 770nF Co (IIC) = 99nF Po = 549mW transmitter met tity parameters Ui <= 30V Li = 0 Ii <= 50mA Ci = 5nF Pi <= 1W aansluitkabel C = 48nF/km L = 0.75mH/km PROFIBUS explosieveiligheid 44
45 Loop calculatie (titeit model) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met zerbarrière safety output parameters : Uo = 28,4V Lo (IIB) = 2mH Lo (IIC) = 0.5mH Io = 24mA Co (IIB) = 370nF Co (IIC) = 79nF Po = 170mW transmitter met tity parameters Ui <= 30V Li = 0 Ii <= 50mA Ci = 5nF Pi <= 1W aansluitkabel C = 48nF/km L = 0.75mH/km PROFIBUS explosieveiligheid 45
46 Loop calculatie (titeit model) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met zerbarrière safety output parameters : Uo = 28,4V Lo (IIB) = 2mH Lo (IIC) = 0.5mH Io = 24mA Co (IIB) = 370nF Co (IIC) = 79nF Po = 170mW transmitter met tity parameters Ui <= 30V Li = 0 Ii <= 75mA Ci = 0 Pi <= 150mW aansluitkabel C = 48nF/km L = 0.75mH/km PROFIBUS explosieveiligheid 46
47 Laatste ontwikkeling Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Introductie van Equipmt Protection Levels in volle gang! EN series EN series Zone ATEX 95 Category EN series (last editions) EPL 0 1G Ga 1 2G Gb 2 3G Gc 20 1D Da 21 2D Db 22 3D Dc PROFIBUS explosieveiligheid 47
48 Wat is e Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS Waterdag
49 Veldbus is zuwstelsel bij de ms Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS Waterdag
50 zuwstelsel in waterbehandelingsinstallatie Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS Waterdag
51 Convtionele oplossing in waterbehandelingsinstallatie Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS Waterdag
52 Zuwstelsel ook geschikt voor Ex veiligheid Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Veiligheid SIL3/CAT.4 PROFIBUS Waterdag
53 Volledig digitaal convtional Analog Process Control Wat is e CPU ma CPU Beschermingsmethodiek DP Ex HART CPU Analog + digital ma smart signal CPU PA Ex PROFIBUS Digital uitwerk met CPU PROFIBUS CPU Grotere nauwkeurigheid van 20% door PROFIBUS Automation Technology Grotere proceskwaliteit Constante proceskwaliteit PROFIBUS Waterdag
54 Meer informatie Wat is e Convtioneel PROFIBUS Beschermingsmethodiek DP Ex PA Ex uitwerk met 15,3 ma Warning: Actuator Actuator starts/run te hoog (aandrijving ontvangt te veel starts per tijdseheid) 1 st value = 70,6 2 nd -n value= eindschakelaar, draaimomt, remote/local,... unit = % or mm status = ok diagnose = ok Oorzaak: Oplossing: Resultaat: het proces is onrustiger dan gepland/verwacht optimaliseer proces door procesinstelling te wijzig levsduurverlging alle apparatuur PROFIBUS Waterdag
55 Situering PROFIBUS Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS Waterdag
56 Zuwstelsel - Plant-Wide Automatisering De oplossing voor alle plant onderdel Wat is e PROFIBUS PROFIBUS PROFIBUS Beschermingsmethodiek DP Ex PA Ex uitwerk met Upstream Inbound Logistics Mainstream Main Production stream Downstream Outbound Logistics PROFIBUS Automation Technology PROFIBUS Waterdag
57 PROFIBUS DP nodes PROFIBUS Nodes 25 m Wat is e 20 m In 2008: 5.0 m nodes! 18.8 m 28.4 m Beschermingsmethodiek DP Ex 15 m At the beginning of 2004, we said: PA Ex 10 m Over the next 4 years, we will double the number of installed PROFIBUS nodes to 20 million. uitwerk met 5 m Time PROFIBUS Waterdag
58 Wat is PROFIBUS? Wat is e Beschermingsmethodiek Van ctrale automatisering-system met e ctrale PLC ssors/actuators gebaseerd op 4-20 ma 0-10 V technologie DP Ex PA Ex uitwerk met via gedistribueerde automatisering-system met e PLC/IPC dectrale periferie PROFIBUS gebaseerd op veldbus technologie e PROFIBUS Waterdag
59 John van Leeuw Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS explosieveiligheid 60
60 Traditionele aanpak (tity concept) Wat is e EEx i interface R, L, C EEx i veld instrumt P o, U o, I o C o, L o P i, U i, I i C i, L i Beschermingsmethodiek DP Ex Procedure: PA Ex uitwerk met Controleer EEx i veiligheid-parameters van alle instrumt Controle voor overestemming: U o =< U i, I o =< I i, P o =< P i...voor elk instrumt Evaluatie van netwerk capaciteit inductie C i + C kabel =< C o L i + L kabel =< L o 61
61 Introductie FISCO Wat is e Beschermingsmethodiek DP Ex Fieldbus Intrinsic Safety Concept E nieuwe technische specificatie voor e EEx i veldbus Maakt gebruik van experimt op vonk ontsteking PA Ex uitwerk met Levert meer stroom aan de EEx i trunk dan vroegere Entity model; er kunn dus meer veldinstrumt word aangeslot Eerste verevoudiging van explosie beveiligingstechniek sinds jar! 62
62 Experimt resultaat Wat is e 1000 m cable 15V Resistive limitation (EEx ia) Gas Group IIC Beschermingsmethodiek DP Ex Supply with cable with Terminators 280 PA Ex uitwerk met Supply with cable Power Supply Ignition currt in ma (Including Safety Factor) Source: Dr. Ulrich Johannsmeyer 63
63 Voordel van FISCO Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Voorhe werd EEx i veldbus installaties uitgevoerd volgs IEC/EN ( Entity ). Hierbij was verplicht: Calculatie van kabel parameters Vergelijk van de veiligheid parameters Mak van e DSD (descriptive system documt) Nu IEC FISCO Technische specificatie Neemt de noodzaak weg om de kabel parameters te berek reduceert veiligheid documtatie tot e lijst van instrumt Staat toe om instrumt toe te voeg zonder de veiligheid documtatie aan te pass Als door tests aangetoond kunn langere kabels met e hogere capaciteit word toegepast 64
64 Het FISCO model geïntroduceerd 1994 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met IEC laat het gebruik van het FISCO model toe. Fieldbus Intrinsic Safety Concept Biedt de gebruikers e duidelijke handleiding voor het ontwerp installer van PROFIBUS PA netwerk in explosie-gevaarlijke ruimtes. DP/PA coupler DP PA 31,25 kbit/s MBP (PROFIBUS PA) Boom Daisy-chain Spur 65
65 Waar is het FISCO model op gebaseerd? Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Elk segmt heeft slechts 1 voedingbron er wordt ge extra voeding op de bus aangebod De veldinstrumt gedrag zich als passieve stroom opnemers (currt sinking) Passieve lijn afsluiting is aangebracht aan beide uiteind van de trunk Lineaire, boom ster netwerk zijn toegestaan Kabellgte gelimiteerd tot: 1 Km in IIC 5 Km in IIB (1900 meter door standaard) Spurlgte gelimiteerd tot: 30 meter (60 meter in nieuwe draft) Elk instrumt: capaciteit inductie gelimiteerd tot Ci < 5 nf, Li < 10 uh 66
66 Het FISCO model Wat is e Het experimt dekte e gedefiniëerd bereik van de kabel parameters, circuit spanning stroom. Daarom zijn de toegestane kabel parameters in e FISCO circuit beperkt tot : Beschermingsmethodiek DP Ex PA Ex Parameter Loop resistance Loop inductance Capacitance Max lgth of each spur cable Max lgth of each trunk cable Value 15 ohm to 150 ohm / km 0.4 mh to 1 mh / km 80 nf to 200 nf / km 60 m in IIC & IIB 1 km in IIC & 5 km in IIB uitwerk met Table 1 - FISCO cable parameters Het is evoudig om binn deze grz te blijv omdat e typische veldbus trunk kabel parameters heeft als: 50 Ω/km, 0,8 mh/km 120 nf/km. De lgte van de trunk is meestal bepaald door de operationele eis. 67
67 Samvatting FISCO Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met FISCO toepasbaar in alle gasgroep explosiegevaarlijke gebied. Het aantal veldinstrumt dat kan word aangeslot op e veldbus segmt wordt alle beperkt door de beschikbare voeding de weerstand van de kabel. Het segmt kan word uitgebreid zonder de noodzaak om nieuwe calculaties uit te voer (binn de grz van het FISCO model). Instrumt van verschillde leveranciers kunn word uitgewisseld zonder de noodzaak om nieuwe calculaties uit te voer. Ge Systeem certificering nodig! 68
68 Samvatting Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Entity badering FISCO applicatie Kabellgte beperkt bij alle gass: 1.9 Km Max spur lgte: 120 m Volledige calculatie van veiligheids parameters Kabellgte limiet: 1 Km in IIC 1.9 Km in IIB Max spur lgte: 60 m Ge verdere kabel parameter overweging nodig Evoudige uitwisseling van instrumt 69
69 FNICO Fieldbus Non-Incdive Concept Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met FNICO is: Voor veldbus in Zone 2 explosiegevaarlijke gebied. Er mag altijd aan de installatie gewerkt word zonder gas clearance, idtiek als bij EEx i. Gebaseerd op FISCO, het Fieldbus Intrinsic Safety Concept. Evoudig te installer, evoudig te documter, evoudig te onderhoud. Met FNICO zijn de trunk spurs Non-incdive. in IEC
70 Zone 2/ EEx n definities Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Non-arcing circuit: Kan hogere spanning stroom niveau s hebb Niet onder spanning aan te werk Kabels moet mechanisch beschermd zijn Ge fout in overweging gom Non-incdive circuit Energie-beperkt tot e lager stroom spanning niveau Als EEx i, echter zonder reking te houd met fout met e lagere veiligheidsfactor (Kan gezi word als EEx ic ) Onder spanning aan te werk Met FNICO zijn trunk spurs Non-incdive 71
71 Samvatting - FNICO Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Biedt de voordel van FISCO: Eliminering van kabel parameter overweging Evoudige documtatie van system Toevoeging van nieuwe instrumt zonder opnieuw de kabel parameters te bezi Onder spanning te werk in het explosie gevaarlijk gebied Met de extra voordel van e Zone 2: Hogere stroom beschikbaar op de trunk door de reductie van de veiligheid factor Meer veldinstrumt per trunk 72
72 Zone 2 DP John Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 73
73 Voordel voor zone 2 classificatie Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Biedt mogelijkhed voor explosiegevaarlijke applicaties teg lagere kost dan EEx i of EEx d. Staat voeding hoog-vermog circuits in het explosiegevaarlijk gebied toe (niet zomaar toegestaan in zone 1 of 0). Gebruikers krijg dezelfde voordel als bij EEx i als het circuit EEx nl (ergie-beperkt) is: onder spanning werk Ssor als 'simpele apparat' 74
74 Normale operationele condities Wat is e Beschermingsmethodiek DP Ex Apparatuur wordt gebruikt onder normale operationele condities als het zowel mechanisch als elektrisch in overestemming is met het originele ontwerp wordt gebruikt binn de grz zoals door de fabricant is gespecificeerd. PA Ex uitwerk met 75
75 Dk es na over normale situaties Halfgeleiders gaan niet kapot Wat is e Beschermingsmethodiek DP Ex PA Ex Zer diodes vorm allee e kortsluiting Weerstand behoud hun weerstands waarde Goed gedimsioneerde zekering gaan niet kapot Transformator isolatie slaat niet door Interconnectie kabels brek niet Klemm compont rak niet los uitwerk met Dit alles kan wel gebeur maar niet regelmatig 76
76 Idtificeer de typ circuits in zone 2 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Non Incdive: Energie-beperkt Veiligheidsfactor éénduidig Laag vermog circuits Onder spanning aan werk NON-ARCING CIRCUITS: Niet-vonkd Hoog vermog voeding circuits Niet onder spanning aan werk Gebruiker moet zorg dat GEEN vonk ontstaan 77
77 Hoe zit dat bij Remote I/O? Non-arcing Wat is e Beschermingsmethodiek DP Ex Voedingspanning aansluiting (bijv. lokale voeding) Non-incdive Interconnectie tuss I/O-modules interne bus is EEx nl; dus onder spanning modules wissel. PA Ex uitwerk met LET OP!!!! Veld circuits van de I/O modules zijn Non-arcing of Non-incdive, of e combinatie van beid. 78
78 Consequties voor PROFIBUS in zone 2 Wat is e Beschermingsmethodiek DP Ex RS-485 Data-interface Mode of operation Differtial Toegestane aantal Tx Rx 32 Tx 32 Rx Maximale kabel lgte (1200 meter) Maximaal driver uitgangsbereik ±6V Maximale driver kortsluitstroom 250mA PA Ex uitwerk met 2 Amps Hydrog group 6 Volts 79
79 Veilig gebruik van RS 485 in zone 2 Uit de specificatie van de PROFIBUS DP blijkt: Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met de maximale op-circuit spanning is ±6V (Driver uitgangsbereik) de maximale kortsluitstroom van 250 ma (Driver kortsluitstroom) Refererd aan de IEC Resistive Ignition Curves geldt: Zelfs voor de gasgroep IIC (Hydrog) is e spanning van 6 volt veilig om te gebruik bij e stroom van maximaal 2.5 A Voor toepassing in Zone 2 is ge noodzaak om safety factor toe te pass op dit ergie niveau 80
80 Veilig gebruik van RS 485 in zone 2 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met In Ex applicaties is het noodzakelijk om reking te houd met de opslag van ergie in de geinstalleerde kabel (door inductie capaciteit). De inductie capaciteit is te vind in het spec.blad van de kabel. De toelaatbare stroom is bepaald door de circuit inductie. Voor IIC gass is de bodigde ergie om e ontsteking te veroorzak= 40 μ Joules De toelaatbare inductie bij 250 ma is 1.28 mh, hetge overekomt met meer dan 1,28 km kabel Voor IIB gass is de bodigde ergie om e ontsteking te veroorzak= 160 μ Joules. De toelaatbare inductie bij 250 ma is 5.12 mh, hetge overekomt met meer dan 5,12 km kabel De toelaatbare spanning is bepaald door de circuit capaciteit. Bij 6 volt is kabel capaciteit irrelevant door de minimale waarde. 81
81 Kast voor zone 2 Wat is e Ex schakelaar ~ De kast zou e Ex e standaard moet zijn als e Ex de gecertificeerde schakelaar intern gemonteerd is. Beschermingsmethodiek DP Ex PA Ex uitwerk met 24 Volt DC of 115/230 Volt AC Voeding tree Ex n type wartel of Ex e type wartel - overtreft type Ex n Gebruik afgeschermde kabel Kast minimum IP54 impact-proof to 7Nm Zekering (optioneel) Acceptabele constructie beschrev in Ex n standard EN De PROFIBUS zekering & PROFINET mag Nederland NIET gebruikt word als afschakel punt 82
82 Ingress Protectie Code IEC / EN Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met First Numeral Protection against solid bodies Second Numeral Protection against liquid No protection 0 0 No protection Objects greater than 50mm 1 1 Vertically dripping water Objects greater than 12mm 2 2 Angled drip. water -75 O to90 O Objects greater than 2.5mm 3 3 Sprayed water Objects greater than 1.0mm 4 4 Splashed water Dust protected 5 5 Water jets Dust-tight 6 6 Heavy seas 7 Effects of immersion 8 Indefinite immersion 83
83 Consequties voor installer Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met ~ PROFIBUS DP (RS485) beschermd voor betrouwbaarheid niet ergie-beperkt voor elektrische veiligheid tzij hoge capaciteit of inductie Bescherming voedingskabel voldo aan Nationale Installatie Standaards (bijv. gearmeerd in NL) I/O Circuits EEX nl of EEX na (gearmeerde kabel) Bij EEx i geld de normale regels voor bekabeling scheiding van andere circuits 84
84 Consequties voor onderhoud Wat is e Beschermingsmethodiek DP Ex Toegang tot systeemkast voor onderhoudwerkzaamhed is geaccepteerd, ervan uitgaande dat: duidelijke instructie gegev is om te voorkom dat er vonk gemaakt word die tot e ontsteking kunn leid; alle bijgevoegde gebruiksaanwijzing duidelijk aangev welke onderhoud acties veilig uitgevoerd kunn word. PA Ex uitwerk met Met andere woord: Idtificeer EEx nl EEX na Circuits 85
85 Indtificeer ExnL ExnA circuits Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Railbus Vcc (+12V) 0V Non-arcing aansluiting tuss I/O module ctrale voeding Ctrale voeding Railbus voeding Non-incdive aansluiting tuss I/O module Railbus Carrier EEx de schakelaar I/O module Naar volgde I/O modules Non-incdive aansluiting tuss I/O module veld circuits EEX nl veld circuits 86
86 Idtificeer ExnL ExnA circuits Wat is e Beschermingsmethodiek DP Ex Ctrale voeding Railbus Vcc (+12V) 0V Non-arcing aansluiting tuss I/O module ctrale voeding EEx de schakelaar Naar volgde I/O modules PA Ex uitwerk met Railbus voeding Non-incdive aansluiting tuss I/O module Railbus Carrier I/O module EEX na aansluiting tuss I/O module veld circuits 87
87 Flexibiliteit in aan te sluit signal Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 88
88 Flexibiliteit in aan te sluit signal Alle signal vanuit veilige explosiegevaarlijke gebied op dezelfde node. Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Zone 2 EEx na + EEx nl Zone 1 EEx d + EEx p Zone 0,1 EEx i Zone 0,1 EEx i 89
89 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 90
90 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 91
91 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 92
92 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 93
93 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Ex i : Ex d : Ex m : Ex q : Ex e : FI Intrinsieke veiligheid, elektronica aanpass Drukvast, standaard elektronica inbouw Ingegot, standaard elektronica ingiet in epoxyhars Zandvulling, standaard elektronica omhull met zand. Verhoogde veiligheid, voornamelijk voor bedrading. LI LIC PI Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 94
94 Zone 1 DP - Marco Wat is e Ex d, q of m Ex e + Ex i Ex i + Ex e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI Ex i + Ex e LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 95
95 Zone 1 DP - Marco Wat is e Ex i Ex i Ex d, q, m Ex e Ex i Beschermingsmethodiek LI PI DP Ex PA Ex uitwerk met DP DP Ex i FI Ex i + Ex e LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 96
96 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP DP Ex i LI PI DP Ex PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 97
97 Zone 1 DP - Marco Wat is e Beschermingsmethodiek LI PI DP Ex DP LWL DP LWL PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 98
98 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP DP Ex i LI PI DP Ex DP LWL DP LWL PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 99
99 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 100
100 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP Ex Remote I/O Systeem Ex II 2G Ex de IIC Digitaal uit 24 VDC, 500 ma LI PI PA Ex uitwerk met Magneetvtiel Ex II 2G EEx m II T4 24 VDC, 10 Watt FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 101
101 Zone 1 DP - Marco Wat is e Remote I/O Systeem Ex II 2G Ex de [ia] IIC Uo = 17.2 V DC Io = 68 ma Beschermingsmethodiek DP Ex PA Ex uitwerk met Magneetvtiel Ex II 2G EEx ia IIC T6 U = V DC Ui = 20 V DC I = 5 66 ma Ii = 85 ma FI LIC LI PI Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 102
102 Zone 1 DP - Marco Wat is e Remote I/O Systeem Ex II 2G Ex de [ia] IIC Uo = 17.2 V DC Io = 68 ma Beschermingsmethodiek DP Ex PA Ex uitwerk met Magneetvtiel Ex II 2G EEx ia IIC T6 U = V DC Ui = 35 V DC I = ma Ii = 85 ma FI LIC LI PI Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 103
103 Zone 1 DP - Marco Wat is e Remote I/O Systeem Ex II 2G Ex de [ia] IIC Uo = 17.2 V DC Io = 68 ma Beschermingsmethodiek DP Ex PA Ex uitwerk met Magneetvtiel Ex II 2G EEx ia IIC T6 U = V DC Ui = 16,5 V DC I = ma Ii = 85 ma FI LIC LI PI Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 104
104 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP DP LI PI DP Ex PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 105
105 Zone 1 DP - Marco Wat is e Beschermingsmethodiek DP Ex Bedankt voor Vrag? LI PI uw aandacht. PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 106
106 Zone 2 PA - Walter Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 107
107 PROFIBUS PA in veilige ruimte Zone 2 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Uitgangspunt definier Stroomverbruik van de voeding Ex specificaties FNICO PROFIBUS in Ex 108
108 Uitgangspunt Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Specificaties segmt Spare voor uitbreiding 20 % Min spanning instrumt 10 V JB met kortsluitbeveiliging 5 ma kabelweerstand 50 Ohm/km Verbruik instrumt 20 ma Voedingspanning 20 V Voedingsstroom 400 ma Verbruik communicatie 10 ma PROFIBUS in Ex 109
109 PROFIBUS PA in veilige ruimte zone 2 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met DP PA MBP Short circuit protection RS 485 Veilige Zone Zone 2 PROFIBUS in Ex 110
110 PROFIBUS PA zone 2 voeding Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met U = 20 V U=20 V I=400mA DP PA MBP Isegm = ma S.C. = ma Belasting = % 50 Ohm/km U min =10V I=20mA/instr S.C.=+25mA Spare = ma Comm = 10 ma L = 500 m Ukabel = RS 485 Veilige Zone R * ma = V Umin = V Zone 2 PROFIBUS in Ex 111
111 PROFIBUS PA zone 2 voeding Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met U=20 V I=400mA U = 20 V DP PA MBP Isegm = 100 ma S.C. = 25 ma Belasting = 31% 50 Ohm/km U min =10V I=20mA/instr S.C.= +25mA Spare = 265 ma Comm = 10 ma L = 500 m Ukabel = RS 485 Veilige Zone 25 R * 100 ma = 2,5 V Umin = 17,5 V Zone 2 PROFIBUS in Ex 112
112 PROFIBUS PA zone 2 voeding Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met U=20 V I=400mA U = 20 V DP PA MBP Isegm = ma S.C. = ma Belasting = % 50 Ohm/km U min =10V I=20mA/instr S.C.=+25mA Spare = ma Comm = 10 ma L = 500 m Ukabel = 15 PA instrumt RS 485 Veilige Zone R * ma = V Umin = V Zone 2 PROFIBUS in Ex 113
113 PROFIBUS PA zone 2 voeding Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met U=20 V I=400mA U = 20 V DP PA MBP Isegm = 300 ma S.C. = 25 ma Belasting = 81% 50 Ohm/km U min =10V I=20mA/instr S.C.=+25mA Spare = 65 ma Comm = 10 ma L = 500 m Ukabel = 15 PA instrumt RS 485 Veilige Zone 25 R * 300 ma = 7,5 V Umin = 12,5 V Zone 2 PROFIBUS in Ex 114
114 PROFIBUS PA zone 2 voeding RS 485 Wat is e U=20 V I=400mA DP PA MBP Veilige Zone Beschermingsmethodiek DP Ex PA Ex uitwerk met U = 20 V Isegm = ma S.C. = ma Belasting = % Spare = ma Comm = 10 ma 50 Ohm/km L = 200 m Ukabel1 = R * ma = V Umin = V L = 50 m Ukabel2 = U min =10V R * ma = V Umin = V I=20mA/instr S.C.=+25mA Zone 2 PROFIBUS in Ex 115
115 PROFIBUS PA zone 2 voeding RS 485 Wat is e U=20 V I=400mA DP PA MBP Veilige Zone Beschermingsmethodiek DP Ex PA Ex uitwerk met U = 20 V Isegm = 200 ma S.C. = 25 ma Belasting = 56% Spare = 165 ma Comm = 10 ma 50 Ohm/km L = 200 m Ukabel1 = 10 R * 200 ma = 2 V Umin = 18 V L = 50 m Ukabel2 = U min =10V 2,5 R * 100 ma = 0,25 V Umin = 17,75 V I=20mA/instr S.C.=+25mA Zone 2 PROFIBUS in Ex 116
116 PROFIBUS PA zone 2 Ex specificatie RS 485 Wat is e U=20 V I=400mA DP PA MBP Veilige Zone Beschermingsmethodiek DP Ex Ex na Ex na PA Ex uitwerk met Ex e Ex na Ex e Ex na Ex na Ex na Zone 2 PROFIBUS in Ex 117
117 Verschill Ex ic (nl) Ex na Ex nl is ic Ex na Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Verificatie van intrinsieke veiligheid (U, I, L, C) Apparataar beschouwd onder normale bedrijfsconditie Ex nl verondersteld LB SC als normaal operatieel bedrijf In US noemt m dit non-incdive field wiring Plugging onder life conditie Intrinsiek veilige installatie Shok proef verplicht Apparataar beschouwd onder normale bedrijfsconditie Ge LB SC onder normaal operationeel bedrijf condition Plugging onder life conditie verbod Verhoogde veiligheid (Ex e) electrische installatie Ge onderscheid tuss Zone 1 Zone 2 installatie Klimaattest verplicht (erg belastd voor ingegot apparatuur) Ex ic (nl) betere specificaties dan na PROFIBUS in Ex 118
118 Verschil Ex ic (nl) Ex i Ex ic (voorhe nl) Ex i Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Houdt ge reking met foutconditie Ge galvanische isolatie Hogere spanning /of capaciteit mogelijk ge fout conditie safety factor 1.0 IEC safety factor van 1.1 voor US requiremts Houdt wel reking met foutconditie tot 2 fout voor cat. 1 apparatuur Galvanische isolatie geprefereerd (voor cat. 1 ass. Apparatus ) Verlaagde spanning /of capaciteit 2 fout conditie safety factor 1.5 Ex ia of b heeft betere specificaties dan ic mag dus ook word gebruikt in e Zone 2 loop PROFIBUS in Ex 119
119 EEx ic (voorhe nl) Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Ex ic is e verevoudigde vorm van intrinsieke veiligheid (gelimiteerde ergie) E verevoudigde Ex loop bereking Segmt Protector Field Device U O = 32 V < U i I O = 45 ma < I i (if available) L O = 0.25 mh > L i + L cable C O = 100 nf > C i + C cable PROFIBUS in Ex 120
120 PROFIBUS PA zone 2 Ex ic specificatie RS 485 Wat is e U=20 V I=400mA DP PA MBP Veilige Zone Beschermingsmethodiek DP Ex Ex nl of i* Ex nl of i* PA Ex uitwerk met Ex e Ex na [nl] Ex?? Ex na [nl] Uuit < Uin Iuit < Iin Cuit > Cinstr + Ckabel Luit > Linstr + Lkabel Ex nl of i* Ex nl of i* Zone 2 PROFIBUS in Ex 121
121 FNICO Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Fieldbus Non-Incdive Concept Doordat Ex nl in de reeds naar Ex ic in de is verhuisd, is FNICO uit de IEC editie 2 verdw. We sprek dus alle nog van FISCO. Huidige ontwikkeling in normcommissie: EN wordt opgehev (!); toekomstig geintegreerd in: EN (product) EN (system) PROFIBUS in Ex 122
122 PROFIBUS PA in veilige ruimte zone 2 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Mogelijkhed voor Profibus Hoog vermog op PA segmt, bus powered instrumtatie Maximale aantal instrumt Maximale kabellgte Combinaties van topologie Combinaties van beschermingswijz DP/PA omzetter in Zone 2 Mogelijkhed voor onderhoud Live maintance, onder voorbehoud bij Ex e d m na. Gasmonitor, werkvergunning Live maintance voor Ex nl circuit PROFIBUS in Ex 123
123 Zone 1 PA - Michiel Wat is e Beschermingsmethodiek DP Ex LI PI PA Ex uitwerk met FI LIC Safe Zone Zone 2 Zone 1 Zone 0 PROFIBUS explosieveiligheid 124
124 PROFIBUS PA in zone 1 zone 0 Method van bescherming Overzicht RS 485 Wat is e DP PA DP PA Veilige Zone Beschermingsmethodiek DP Ex MBP-IS FISCO / Entity Eex e Multibarriere Zone 2 PA Ex uitwerk met Eex d MBP MBP-IS FISCO / Entity Zone 1 Zone 0 PROFIBUS in Ex 125
125 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Consequties voor Profibus PA ATEX eist Categorie 2 of 1 (G of D) netwerk compont Beperking deelnemers voor I.S. Niet live aan installatie werk Eex e / d Gecertificeerde behuizing Gecertificeerde afsluitweerstand Certificering door Notified body Kleur gebruik van PA kabel PROFIBUS in Ex 126
126 PROFIBUS PA in zone 1 zone 0 Intrinsieke veiligheid FISCO / Entity Toepassing in zone 1 0 RS 485 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met DP PA MBP-IS FISCO / Entity Veilige Zone Zone 2 Zone 1 Zone 0 PROFIBUS in Ex 127
127 PROFIBUS PA in zone 1 zone 0 Wat is e Het FISCO Model: Omvat kabelparameters, circuit spanning stroom. Daarom zijn de toegestane kabel parameters in e FISCO circuit beperkt tot : Beschermingsmethodiek DP Ex PA Ex Parameter Loop resistance Loop inductance Capacitance Max lgth of each spur cable Max lgth of each trunk cable Value 15 ohm to 150 ohm / km 0.4 mh to 1 mh / km 80 nf to 200 nf / km 60 m in IIC & IIB 1 km in IIC & 1.9 km in IIB uitwerk met Table 1 - FISCO cable parameters Het is evoudig om binn deze grz te blijv omdat e typische veldbus trunk kabel parameters heeft als: 50 Ω/km, 0,8 mh/km 120 nf/km. De lgte van de trunk is meestal bepaald door de operationele eis. PROFIBUS in Ex 128
128 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Entity vs FISCO Entity Kabellgte beperkt bij alle gass: 1.9 Km Max spur lgte: 120 m Volledige calculatie van veiligheidsparameters FISCO Kabellgte limiet: 1.0 Km in IIC 1.9 Km in IIB Max spur lgte: 60 m Ge verdere kabelparameter overweging nodig Evoudige uitwisseling van instrumt PROFIBUS in Ex 129
129 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Intrinsieke veiligheid - FISCO of Entity Flexibiliteit in instrumtatiekeuze: Ex ia of ib gecertificeerd Voor FISCO apart certificaat of aanvulling Flexibiliteit in fysiek netwerk: In het instrumt Met T stukk Met Junction Boxes Meervoudige aansluiting Met of zonder kortsluitbewaking Met of zonder geïntegreerde afsluitweerstand IP 20 of IP67 Kabel voor PA kleur BLAUW PROFIBUS in Ex 130
130 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Eex e icm Eex d Toepassing in zone 1 DP PA Eex e Eex d MBP RS 485 Veilige Zone Zone 2 Zone 1 Zone 0 PROFIBUS in Ex 131
131 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Eex e icm Eex d Flexibiliteit in instrumtatiekeuze: Alle Eex d gecertificeerde apparatuur Flexibiliteit in fysiek netwerk: In het instrumt Met Junction Boxes Eex e of Eex d Meervoudige aansluiting Met of zonder kortsluitbewaking Met of zonder geïntegreerde afsluitweerstand Standaard PA kabel PROFIBUS in Ex 132
132 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex PA Ex Eex e icm Intrinsieke veiligheid Multibarriere Toepassing in zone 1 0 DP PA Eex e Multibarriere RS 485 Veilige Zone Zone 2 uitwerk met MBP Live aan de hoofdkabel (Eex e) werk NIET mogelijk MBP-IS FISCO / Entity Zone 1 Live aan de instrumt werk mogelijk (IS), zowel zone 1 als 0 Zone 0 PROFIBUS in Ex 133
133 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Eex e icm IS Multibarriere Flexibiliteit in instrumtatiekeuze: Ex ia of ib gecertificeerd Voor FISCO apart certificaat of aanvulling Flexibiliteit in fysiek netwerk: Met Junction Boxes Eex e Meervoudige aansluiting Met of zonder kortsluitbewaking Met of zonder geïntegreerde afsluitweerstand Eex e kabel is standaard PA kabel Kabelkleur IS aansluiting Multibarriere: BLAUW PROFIBUS in Ex 134
134 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met Specificaties PA netwerk Spare voor uitbreiding 20 % Voedingspanning 24 V Voedingsstroom 400 ma Kabelweerstand 50 Ohm/km Min. spanning Multibarriere 16 V MB met kortsluitbeveiliging 40 ma Verbruik instrumt 20 ma Verbruik communicatie 10 ma Kan de volgde applicatie functioner? PROFIBUS in Ex 135
135 PROFIBUS PA in zone 1 zone 0 Eex e icm Intrinsieke veiligheid Multibarriere Rekvoorbeeld op basis van FISCO RS 485 Wat is e DP PA 24 V 400 ma Veilige Zone Beschermingsmethodiek DP Ex 400 m 40 ma Zone 2 PA Ex uitwerk met 50 Ohm/km SPARE 200 m 400 m Zone 1 20 ma Zone 0 PROFIBUS in Ex 136
136 PROFIBUS PA in zone 1 zone 0 Wat is e DP PA Eex e icm Intrinsieke veiligheid Multibarriere Uitwerking rekvoorbeeld 24 V 400 ma Totale stroomopname: 3x40mA + 6x20mA = 240 ma + 10 ma communicatie = 250 ma RS 485 Veilige Zone Beschermingsmethodiek Uin Multibarriere 2: 19 -/- (0,17x(0,2x50)) = 17,3V DP Ex 400 m Uin Multibarriere 3: 17,3 -/- (0,09x(0,4x50)) = 15,5V 40 ma Zone 2 PA Ex uitwerk met 50 Ohm/km Uin Multibarriere 1: 24 -/- (0,25x(0,4x50)) = 19V SPARE 200 m 400 m Zone 1 20 ma Zone 0 PROFIBUS in Ex 137
137 PROFIBUS PA in zone 1 zone 0 Wat is e Beschermingsmethodiek DP Ex Uit voorgaande rekvoorbeeld is te concluder dat de laatste multibarriere niet kan functioner. Door minder instrumt aan te sluit, de afstand te verklein is dit evtueel wel mogelijk. E hogere uitgangsspanning van de DP/PA coupler kan ook uitkomst bied. PA Ex uitwerk met Einde PROFIBUS in Ex 138
138 Convtioneel, PROFIBUS DP of PROFIBUS PA Schakelkast Schakelkast Schakelkast PLC mainrack PLC mainrack PLC mainrack Wat is e PLC I/O rack PLC I/O rack Profibus DP/PA convertor Beschermingsmethodiek DP Ex PA Ex Veld Rack versterkers klemm strok Multicore kabel Veld Rack versterkers klemm strok Multicore Profibus kabel kabel Veld Profibus kabel uitwerk met Junction box Junction Remote box I/O T P L Transmitters T T P L Transmitters T T P L Transmitters T PROFIBUS explosieveiligheid 139
139 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS explosieveiligheid 140
140 Wat is e Beschermingsmethodiek DP Ex PA Ex uitwerk met PROFIBUS explosieveiligheid 141
De PROFINET, PROFIBUS & IO-Link dag. 7 juni 2012
De PROFINET,. PROFIBUS & IO-Link dag 7 juni 2012 Profibus ook de juiste techniek in applicaties met explosie risico Onderwerpen 3 Explosie driehoek Temperatuur- en gasklassen Zonering Apparaat markeringen
Nadere informatieProfibus ook de juiste techniek in applicaties met explosie risico.
De PROFINET, PROFIBUS & IO-Link dag Profibus ook de juiste techniek in applicaties met explosie risico. 2011 John van Leeuwen Explosie driehoek 2 Ontstekingsbron Warmte Vonk Gas Stof ATEX Lucht Eigenschappen
Nadere informatieStappenplan voor het explosieveiligheidsdocument. In een onderzoek kunnen de volgende stappen genomen worden:
ATEX introductie De Atex richtlijn is van toepassing op alle plaatsen waar ontploffingsgevaar kan heersen. De richtlijn heeft een breed werkingsgebied en omvat naast gasexplosiegevaar ook stofexplosiegevaar.
Nadere informatieInstallatie van Elektrische apparatuur in ATEX zones. IECEx 05 Ex
Installatie van Elektrische apparatuur in ATEX zones IECEx 05 Ex 003 + 006 Voorstellen Ir. Andries Brakke IAB Ingenieurs te Appingedam (NL) IECEX 05 gecertificeerd Opzetten en geven van trainingen op het
Nadere informatieSAFETY CLASS, Programma 2010
SAFETY CLASS, Programma 2010 Wilt u een - pert worden? In de markt van explosieveiligheid gaan de ontwikkelingen in een steeds sneller tempo. Denk bijvoorbeeld aan de zone 2 toepassingen en de opmars van
Nadere informatieSAFETY CLASS, Programma 2012-2013
SAFETY CLASS, Programma 2012-2013 Wilt u een - pert worden? In de markt van explosieveiligheid gaan de ontwikkelingen in een steeds sneller tempo. Denk bijvoorbeeld aan de zone 2 toepassingen en de opmars
Nadere informatieATEX installatieinstructies. Micro Motion CMF400- sensoren met hulpversterker
Installatie-instructies P/N MMI-20010156, Rev. A Juni 2007 ATEX installatieinstructies voor Micro Motion CMF400- sensoren met hulpversterker Voor de installatie van sensors met ATEX-goedkeuring Opmerking:
Nadere informatieKwaliteit in de Explosieveiligheid
Kwaliteit in de Explosieveiligheid Even voorstellen Christian Cameron: Kwaliteitsmanager 16 jaar ervaring in kwaliteitsmanagement. Verantwoordelijk voor KAM, kennisborging mbt explosieveiligheid en deels
Nadere informatie0 Normen en principes
1 EN / IEC normen... 5 2 Beschermingswijzen... 6 3 Indeling in groepen en temperatuurklassen... 8 4 Indeling in zones en keuze van materieel (= categorieën)... 9 5 Equipment Protection Level... 10 6 Certifi
Nadere informatieHoe veilig is úw installatie? Karel Neleman BARTEC
Hoe veilig is úw installatie? Karel Neleman BARTEC 1 Weet u waar u op moet letten? Wees bedacht op schijnveiligheid 2 Gebruik de norm! 3 Wie past installatienorm toe? Soort bedrijven Bedrijven met enige
Nadere informatieVEILIGHEID IS MEER DAN SIL ATEX EXPLOSIEVEILIGHEID. 20 september 2017 Practical Safety Event 1
VEILIGHEID IS MEER DAN SIL ATEX EXPLOSIEVEILIGHEID 20 september 2017 Practical Safety Event 1 WAT WE WILLEN VOORKOMEN Buncefield Engeland 11 December 2005 Grootste explosie sinds de tweede wereldoorlog;
Nadere informatieSAFETY CLASS, Programma 2012
SAFETY CLASS, Programma 2012 Wilt u een - pert worden? In de markt van explosieveiligheid gaan de ontwikkelingen in een steeds sneller tempo. Denk bijvoorbeeld aan de zone 2 toepassingen en de opmars van
Nadere informatieHarsh & Hazardous. Dé richtlijnen voor extreme omstandigheden EXPLOSIES
Harsh & Hazardous Dé richtlijnen voor extreme omstandigheden EXPLOSIES Explosies Een explosie is het plotseling vergroten van het volume van een hoeveelheid materie waarna de energie op een heftige manier
Nadere informatieE69F Elektro-pneumatische signaalomvormer en E69P Elektro-pneumatische klepstandsteller. Veiligheidsinformatie
Voorschrift MI 018-429 Juni 2005 E69F Elektro-pneumatische signaalomvormer en E69P Elektro-pneumatische klepstandsteller Veiligheidsinformatie Ga naar het website-adres hieronder voor veiligheidsinformatie
Nadere informatieEnergie besparing & ATEX
Energie besparing & ATEX gaat dat samen? Even voorstellen Drs Ing Joris Bracke Uneto-VNI Voorzitter Vakgroep Elektromechanisch Onderhoud Directeur EB-groep Elektromotoren Bracke (Clinge, NL) Boer en Bakker
Nadere informatie0 Normen en principes
1 EN / IEC normen... 7 2 Beschermingswijzen... 8 3 Indeling in groepen en temperatuurklassen... 10 4 Indeling in zones en keuze van materieel (= categorieën)... 12 5 Equipment Protection Level... 13 6
Nadere informatieInstallatie-instructies P/N MMI , Rev. A februari ATEX installatie-instructies voor Micro Motion Model LFT Low Flow-transmitters
Installatie-instructies P/N MMI-20011729, Rev. A februari 2009 ATEX installatie-instructies voor Micro Motion Model LFT Low Flow-transmitters Opmerking: Voor installatie in een explosiegevaarlijke omgeving
Nadere informatieProductnietlangerleverbaar'
Speciale veiligheidsinstructie Tankmeetsysteem Speciale veiligheidsinstructie ATEX Productnietlangerleverbaar' www.rosemount-tg.com Speciale veiligheidsinstructie Rosemount TankRadar REX Inhoudsopgave
Nadere informatieATEX installatieinstructies. Micro Motion T-serie-sensoren
Installatie-instructies P/N MMI-20010113, Rev. A Juni 2007 ATEX installatieinstructies voor Micro Motion T-serie-sensoren Voor de installatie van sensors met ATEX-goedkeuring Opmerking: Voor installatie
Nadere informatieIn dit boekje vindt u hieromtrent handige en praktische informatie.
Pocket Introductie Bij de productie, verwerking, stockage en transport van ontvlambare producten komen onvermijdelijk gassen vrij. In combinatie met lucht vormt dit een explosief mengsel. Een vonk, of
Nadere informatieHandleiding Explosieveilig timerrelais Type AR-023. II 3 D Ex tc IIIC T80ºC Dc
Handleiding Explosieveilig timerrelais Type AR-023 II 3 G Ex na mc IIC T6 Gc II 3 D Ex tc IIIC T80ºC Dc 1. Veiligheidsinstructies Het AR-023 timerrelais is een explosieveilig product dat geschikt is voor
Nadere informatieRADAR-NIVEAUMETER SPECIALE VEILIGHEIDSINSTRUCTIE
Speciale veiligheidsinstructie du RADAR-NIVEAUMETER SPECIALE VEILIGHEIDSINSTRUCTIE Inhoudsopgave Informatie over de Europese ATEX-richtlijn voor de TankRadar Pro.................... 2 ATEX-markering en
Nadere informatieCertificering van Skids & Assemblies: zin of onzin? Karel Neleman BARTEC
Certificering van Skids & Assemblies: zin of onzin? Karel Neleman BARTEC 1 Wie ben ik? >25 jaar ervaring in elektrische explosieveiligheid bij >15 jaar lid van de Nederlandse normcommissie Deelnemer in
Nadere informatieBasics of Asset Management
Nationale Profibusdag 18 november Ede Walter Stoops Pepperl+Fuchs Ontwikkeling 2 ATE 20 MB X>500 GB Windows 1.0 Windows 3.** Windows 95 Windows ME Windows XP Windows Vista Windows 7 90 00 10 20 tijd Nationale
Nadere informatieATEX installatieinstructies. Micro Motion F-seriesensoren DMT 01 ATEX E 158 X
Installatie-instructies P/N MMI-20010178, Rev. A Juni 2007 ATEX installatieinstructies voor Micro Motion F-seriesensoren met certificaat DMT 01 ATEX E 158 X Voor de installatie van sensors met ATEX-goedkeuring
Nadere informatieApplicatie zuurstofmonitor M1000
M1000 applicatie EX Applicatie zuurstofmonitor M1000 Door het combineren van beschermingswijzen is het mogelijk om tot praktische oplossingen te komen voor toepassingen in explosiegevaarlijke gebieden.
Nadere informatieATEX voor beginners ; explosiegevaar in vogelvlucht
ATEX voor beginners ; explosiegevaar in vogelvlucht Waarom doen we aan ATEX Het doel is mensen beschermen tegen de effecten van een explosie Wat is een explosie eigenlijk? Een momentane ontbranding van
Nadere informatieInductieve sensor BI2-EM12-Y1X-H1141
ATEX categorie II 1 G, Ex zone 0 ATEX categorie II 1 D, Ex zone 20 SIL2 volgens IEC 61508 schroefdraad, M12 x 1 roestvaststaal, 1.4301 DC 2-draads, nom. 8,2 VDC uitgang volgens DIN EN 60947-5-6 (NA- MUR)
Nadere informatieHART en 4 20 ma integreren in een PROFIBUS-installaties
PROFIBUS, PROFINET HART en 4 20 ma integreren in een PROFIBUS-installaties Edegem, 10 juni 2009 De Uitdaging 1 Het is noodzakelijk om een productieinstallatie te herzien in een zeer korte tijd met weinig
Nadere informatieATEX samenstellingen. Michiel Bakker MiBEx
ATEX samenstellingen Michiel Bakker MiBEx Wie ben ik? ATEX en IECEx specialist Consultant Nieuwe en bestaande apparatuur Elektrisch en niet-elektrisch Trainer Fabrikanten Installateurs Monteurs / operators
Nadere informatieProduct information Scheidingsversterkers en Beveiliging
Product information Overspanningsbeveiligingen B-9 B6-00, B6-00 FI B6-6G, B6-0W B6-, B6-8 B8- Document ID: 0707 Inhoudsopgave Inhoudsopgave Productbeschrijving... Type-overzicht... Elektrische aansluiting...
Nadere informatieFiche 23 (Expertise): Artikels van het AREI aangaande het explosie gevaar
Fiche 23 (Expertise): Artikels van het AREI aangaande het explosie gevaar Bepalen op welke plaatsen een explosie zich kan voordoen. Dit moet gebeuren in samenwerking met een erkend organisme. Het rapport
Nadere informatieMechanische apparatuur onder ATEX 114 en IECEx 02. Leo van Schie Certification Manager Explosion Safety
Mechanische apparatuur onder ATEX 114 en IECEx 02 Leo van Schie Certification Manager Explosion Safety Leo van Schie 14 jaar werkzaam voor DEKRA Projectleider en Certificatie Manager explosieveiligheid
Nadere informatieDe PROFIBUS, PROFINET & IO-Link dag. Edegem, 8 juni 2010. PROFIBUS Belgium VZW PROFIBUS, PROFINET & IO-Link
De PROFIBUS, PROFINET & IO-Link dag Edegem, 8 juni 2010 PROFIBUS Belgium VZW PROFIBUS, PROFINET & IO-Link 2010 Profibus in de procesindustrie 2 Jaap Westeneng PROFIBUS in de procesindustrie Aansluiting
Nadere informatieInstallatie Instructies P/N 20004418, Rev. C Juni 2008. Voor transmitterinstallaties met ATEX-goedkeuring
Installatie Instructies P/N 20004418, Rev. C Juni 2008 ATEX installatieinstructies en tekeningen Voor transmitterinstallaties met ATEX-goedkeuring Opmerking: Voor installatie in een explosiegevaarlijke
Nadere informatieElektromechanisch koppelvlak voor LEDsignaalgevers. Profibus DP. jklmnopq. Technical Specification. 14 juli Ministerie van Verkeer en Waterstaat
Ministerie van Verkeer en Waterstaat jklmnopq Adviesdienst Verkeer en Vervoer Elektromechanisch koppelvlak voor LEDsignaalgevers Profibus DP Technical Specification 14 juli 2005 1999, Transport Research
Nadere informatieInstallatie-instructies P/N MMI , Rev. A September ATEX installatie-instructies voor Micro Motion MVD Direct Connect -meters
Installatie-instructies P/N MMI-20011728, Rev. A September 2008 ATEX installatie-instructies voor Micro Motion MVD Direct Connect -meters Opmerking: Voor installatie in een explosiegevaarlijke omgeving
Nadere informatieDe nieuwe installatienorm en de consequenties hiervan. Karel Neleman
De nieuwe installatienorm en de consequenties hiervan Karel Neleman 1 Wie ben ik? 24 jaar ervaring in elektrische explosieveiligheid bij 15 jaar lid van normcommissie NEC 31 Internationaal Maintenance
Nadere informatieHART en 4 20 ma integreren in een PROFIBUS-installaties
HART en 4 20 ma integreren in een PROFIBUS-installaties Edeg, 12 november 2009 De reden De reden voor het initiëren van zo n project kan het verbeteren van de productie en of veiligheid zijn. De Nationale
Nadere informatieHART en 4 20 ma integreren in een PROFIBUS-installaties
PROFIBUS Nederland PROFIBUS, PROFINET HART en 4 20 ma integreren in een PROFIBUS-installaties Edegem, 8 juni 2010 De reden De reden voor het initiëren van zo n project kan het verbeteren van de productie
Nadere informatieGebruiksaanwijzing Inductieve naderingsschakelaar NAMUR. Sachnr /01 08/04 NE****/ NF****/ NG****/ NI****/ NN****/ NT****/ NS****
Gebruiksaanwijzing Inductieve naderingsschakelaar NAMUR Sachnr. 701635/01 08/04 / / / NI****/ / / Aanwijzingen voor het veilige gebruik in explosieve omgevingen Gebruik volgens de voorschriften Gebruik
Nadere informatieINHOUD INLEIDING. Hoofdstuk 1 EXPLOSIES 1 1.1 FYSISCHE EXPLOSIES 3 1.2 CHEMISCHE EXPLOSIES 3 1.3 DEFLAGRATIE EN DETONATIE 4
INLEIDING XV Hoofdstuk 1 EXPLOSIES 1 1.1 FYSISCHE EXPLOSIES 3 1.2 CHEMISCHE EXPLOSIES 3 1.3 DEFLAGRATIE EN DETONATIE 4 1.4 INWENDIGE EN VRIJE EXPLOSIES 6 1.5 GAS- EN STOFEXPLOSIES 6 1.6 EXPLOSIE-EFFECTEN
Nadere informatieDe PROFIBUS & PROFINET dag 2009. Edegem, 10 juni 2009
De PROFIBUS & PROFINET dag 2009 Edegem, 10 juni 2009 Wat is PROFIBUS? Ronald Poosen PI Competence Center ACRO 2 Waarom PROFIBUS - Centrale PLC - Sensoren/Actuatoren - Gebaseerd op 4-20mA of 0-10V technologie
Nadere informatieMURRELEKTRONIK IO-LINK, EN NU? Roel Janssen
MURRELEKTRONIK IO-LINK, EN NU? Roel Janssen MURRELEKTRONIK Onze systemen en waar u deze kan tegenkomen. Elektronica in de schakelkast I/O-Systemen Automotive Interfaces Aansluittechniek Werktuigmachine
Nadere informatieSET/TSH2- en SET/TSHS2
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.7.2016 Internet: www.labkotec.fi 1/7 SET/TSH2- en SET/TSHS2 Capacitieve niveausensoren Auteursrecht 2016
Nadere informatieTAP connector voor LED-signaalgevers Profibus DP
Ministerie van Verkeer en Waterstaat jklmnopq Adviesdienst Verkeer en Vervoer TAP connector voor LED-signaalgevers Profibus DP Technical Specification 14 juli 2005 1999, Transport Research Center (AVV).
Nadere informatieem4 Toebehoren Analoge uitbreidingen
em4 Toebehoren en Uitbreidingen voor analoge ingangen en statische uitgangen om een groter aantal sensoren en schakelaars te verbinden aan uw PLC Er kunnen tot twee dezelfde of verschillende uitbreidingen
Nadere informatieCertificeringsplicht van samenstellingen?
Certificeringsplicht van samenstellingen? Even voorstellen.. Ontwikkeling, certificering, project support Opleiding, kennis borging en kenniscentrum Explosieveiligheid, intrinsieke- en functionele veiligheid
Nadere informatieRub-Block RB100DN met PT100 sensor
Rub-Block RB100DN met PT100 sensor Inhoudsopgave 1. Toepassing 3 2. Waarschuwingen en symbolen in deze gebruiksaanwijzing 3 3. Functie 3 3.1 Rub-Block met PT100 sensor 3 3.2 Meetomvormer optioneel 4 4.
Nadere informatieAVID standaanwijzers. Het assortiment. CR standaanwijzer Corrosiebestendige IP68 standaanwijzer voor afsluiters.
AVID Het assortiment AVID (Automated Valve Interface Devices) standaanwijzers omvat de meest geavanceerde technologie voor het bewaken en sturen van geautomatiseerde kwartslag afsluiters Alle AVID producten
Nadere informatieIntroductie Capa Switch KLS 100 - Algemeen
Introductie Capa Switch KLS 100 - Algemeen Opmerking: De Capa Switch KLS 100 mag alleen worden toegepast zoals omschreven in deze gebruiksaanwijzing. De Capa Switch KLS 100 capacitieve niveauschakelaar
Nadere informatieThe cabling is the easiest part of bus systems..
www.procentec.comcom info@procentec.comcom 1 A few words of some inexperienced engineers and marketeers: he cabling is the easiest part of bus systems.. Yeah right!!!!! 2 Copyrights by PROCENEC 2009 1
Nadere informatieATEX installatie-instructies voor Micro Motion ELITE -sensors
Installatie-instructies P/N MMI-20010080, Rev. B December 2007 ATEX installatie-instructies voor Micro Motion ELITE -sensors Voor de installatie van sensors met ATEX-goedkeuring NB: Voor installatie in
Nadere informatieGASDETECTOR ST400EC ART.NR
DATA SHEET 1(7) GASDETECTOR ST400EC ART.NR. 1217502-1217521 DETECTIE VAN TOXISCHE GASSEN EN ZUURSTOF SYSTEEM GS5000, GS3000, SW2020, BUCONTROL / BUTOUCH ALGEMENE INFORMATIE Detectie van giftige gassen
Nadere informatieProject tankopslag. Onderdeel 3: Dampverwerkingsinstallaties/ Explosieveiligheid. - Zone 0 beleid - Dampverwerking
Project tankopslag Onderdeel 3: Dampverwerkingsinstallaties/ Explosieveiligheid - Zone 0 beleid - Dampverwerking Project tankopslag, dampverwerking/explosieveiligheid oktober 2012 Explosieveiligheid in
Nadere informatieATEX REGELGEVING Regels en voorschriften voor apparaten, arbeidsmiddelen en arbeidsplaatsen in explosieve omgevingen
ATEX REGELGEVING Regels en voorschriften voor apparaten, arbeidsmiddelen en arbeidsplaatsen in explosieve omgevingen Sinds 30 juni 2003 is er het één en ander veranderd voor apparaten en beveiligingssystemen
Nadere informatieKEYSTONE. OM8 - EPI 2 AS-Interface module Handleiding voor installatie en onderhoud. www.pentair.com/valves
KEYSTONE Inhoud 1 Optionele module 8: AS-Interface module 1 2 Installatie 1 3 Communicatiekenmerken 1 4 Beschrijving van de OM8 AS-Interface module 2 5 AS-Interface protocol 3 6 Communicatie-interface
Nadere informatieHandleiding. Explosieveilige SpotLED Type AR-040. II 3 G Ex na IIC T4 Gc II 3 D Ex tc IIIC T135ºC Dc
Handleiding Explosieveilige SpotLED Type AR-040 II 3 G Ex na IIC T4 Gc II 3 D Ex tc IIIC T135ºC Dc 1. Veiligheidsinstructies De AR-040 SpotLED is een explosieveilig product dat geschikt is voor gebruik
Nadere informatieHandleiding. Explosieveilige schemerschakelaar Type AR-022. II 3 G Ex nr IIC T6 Gc II 3 D Ex tc IIIC T80ºC Dc
Handleiding Explosieveilige schemerschakelaar Type AR-022 II 3 G Ex nr IIC T6 Gc II 3 D Ex tc IIIC T80ºC Dc 1. Veiligheidsinstructies De AR-022 schemerschakelaar is een explosieveilig product dat geschikt
Nadere informatieOMS-1 Alarmtoestel olieafscheider Installatie- en bedieningsinstructies
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 20.4.2012 Internet: www.labkotec.com 1/12 OMS-1 Alarmtoestel olieafscheider Copyright 2012 Labkotec Oy Wij
Nadere informatieOntwerpen van PROFIBUS installaties. Geert Leen PROFIBUS International Competence Center ACRO
Ontwerpen van PROFIBUS installaties Geert Leen PROFIBUS International Competence Center ACRO Ontwerpen van een PROFIBUS installatie Keuze van het kabeltype Standaard kabel Halogeenvrije FRNC kabel Kabel
Nadere informatieATEX installatieinstructies. Micro Motion H-seriesensoren
Installatie-instructies P/N MMI-20010102, Rev. A Juni 2007 ATEX installatieinstructies voor Micro Motion H-seriesensoren Voor de installatie van sensors met ATEX-goedkeuring Opmerking: Voor installatie
Nadere informatieMagneetveld-sensor magneetinductieve naderingssensor BIM-EG08-Y1X
ATEX categorie II 1 G, Ex zone 0 ATEX categorie II 1 D, Ex zone 20 SIL2 volgens IEC 61508 schroefdraad, M8 x 1 roestvast staal, 1.4427 SO nominale schakelafstand 78 mm, in combinatie met magneet DMR31-15-5
Nadere informatieINSTALLATIE EN BEDIENINGS HANDLEIDING
Oilset-1000 Handleiding voor installatie en werking Januari 2010 OilSET-1000 ALARM UNIT voor Olie-afscheiders INSTALLATIE EN BEDIENINGS HANDLEIDING INHOUDSOPGAVE 1. ALGEMEEN. 3 2. INSTALLATIE 4 2.1 OilSET-1000
Nadere informatiePDM-8-MB POM (VOEDING OVER MODBUS) Montage & gebruiksvoorschriften
POM ( MODBUS) Montage & gebruiksvoorschriften Inhoudstafel VEILIGHEIDS - & VOORZORGSMAATREGELEN 3 PRODUCTBESCHRIJVING 4 GEBRUIKSTOEPASSING 4 TECHNISCHE GEGEVENS 4 STANDAARDEN 4 OPERATIONELE DIAGRAMMEN
Nadere informatieInstallatie-instructies P/N MMI , Rev. A September ATEX installatie-instructies voor Micro Motion - transmitters, model 2200
Installatie-instructies P/N MMI-20013045, Rev. A September 2008 ATEX installatie-instructies voor Micro Motion - transmitters, model 2200 NB: Voor installatie in een explosiegevaarlijke omgeving in Europa
Nadere informatieHandleiding. Explosieveilige rooftop airconditioner Type serie AR-053
Handleiding Explosieveilige rooftop airconditioner Type serie AR-053 II 3 G Ex ic na mc h IIC T3 Gc 1. Veiligheidsinstructies De explosieveilige rooftop airconditioner serie AR-053 is een explosieveilig
Nadere informatieDubbel besparen met ASi-Safe
Dubbel besparen met ASi-Safe Edegem, 10 juni 2009 Even voorstellen EUCHNER Benelux Normcommissie NEC44 SafetyPlaza De PROFINET & IO-Link dag 2009 2 De EUCHNER organisatie EUCHNER GmbH + Co. KG Fabrikant
Nadere informatie: rev. 2 aanvulling gegevens testen stofexplosie risico zinkstof en VOORSCHRIFT REGELS MET BETREKKING TOT GAS- OF STOFEXPLOSIEGEVAAR
Gezien en akkoord bevonden door: Manager Maintenance & Engineering J. Kouw Arbeidshygiënist E. Schuurmans Production Manager J. Kouw Hoofd Veiligheid H. van den Elsen Aard van de laatste wijziging aanvulling
Nadere informatieUpdate Installatie richtlijn Explosiegevaarlijk gebied
Update Installatie richtlijn Explosiegevaarlijk gebied NEN-EN-IEC 60079-14 Electromach B.V. Jos Abbing (abbing@electromach.nl) Introductie Jos Abbing Electromach b.v. Ruim 15 jaar ervaring in explosieveiligheid
Nadere informatieMagneetveld-sensor voor pneumatische cilinders BIM-UNT-AY1X/S1139
ATEX categorie II 1 G, Ex zone 0 ATEX categorie II 1 D, Ex zone 20 Voor cilinder met T-gleuf zonder montagetoebehoren Optionele toebehoren voor de montage op andere cilinderbouwvormen montage met één hand
Nadere informatieHandleiding. Explosieveilige raam airconditioner Type serie AR-054. II 3 G Ex ic nac h IIC T3 Gc
Handleiding Explosieveilige raam airconditioner Type serie AR-054 II 3 G Ex ic nac h IIC T3 Gc 1. Veiligheidsinstructies De explosieveilige raam airconditioner serie AR-054 is een explosieveilig product
Nadere informatieExplosieveiligheid en ATEX
Explosieveiligheid en ATEX Wet- en regelgeving en beschermingstechnieken John van Leeuwen Regional Industry Manager Process North Europe KIVI NIRIA, 17 september 2013 Weidmüller Facts & Figures Short Profile
Nadere informatieEXPLOSIEVEILIGHEIDSDOCUMENT Beoordeling van explosiegevaren door gas en damp van binnen arbeidsplaatsen
Explosiegevaarlijke ruimte: Arbeidsplaats: Beschrijving van gas en/of damp Veiligheidsinformatieblad aanwezig (1) Vlampunt Vlampunt beneden 21 C Vlampunt boven 21 C Beschrijving van de installatie (2)
Nadere informatieCapacitieve sensor BC10-S30-Y1X/S90
ATEX-categorie II 2 G, Ex-zone 1 ATEX categorie II 1 D, Ex-zone 20 SIL2 (Low Demand Mode) conform IEC 61508, PL c conform ISO 13849-1 bij HFT0 SIL3 (All Demand Mode) conform IEC 61508, PL e conform ISO
Nadere informatieExplosieveilige Insteekbundel Type D-8530
Explosieveilige Insteekbundel Type D-8530 Voor risicovol gebied heeft Sinus Jevi Ex de verwarmingsapparatuur ontworpen en gefabriceerd. De explosieveilige (d) behuizingen zijn ontworpen voor niet veilige
Nadere informatieNieuwe ontwikkelingen. Op het gebied van zone-indeling m.b.t. gas- en stofexplosiegevaar
Nieuwe ontwikkelingen Op het gebied van zone-indeling m.b.t. gas- en stofexplosiegevaar Introductie Gerdian Jansen (Consultant HSE) gja@hse-advies.nl HSE- ADVIES B.V. (HSE-Advies is een onderdeel van de
Nadere informatieMontage-, gebruiks- en onderhoudsaanwijzing voor. Jola-contactbeschermrelais KR 5/Ex I (M1) / II (1) GD [Ex ia Ma] I [Ex ia Ga] IIC [Ex ia Da] IIIC
Montage-, gebruiks- en onderhoudsaanwijzing 1/6 Montage-, gebruiks- en onderhoudsaanwijzing Jola-contactbeschermrelais KR 5/Ex I (M1) / II (1) GD [Ex ia Ma] I [Ex ia Ga] IIC [Ex ia Da] IIIC Deze montage-,
Nadere informatieVentielen voor de Procesindustrie Doordachte Pneumatiek Oplossingen
Ventielen voor de Procesindustrie Doordachte Pneumatiek Oplossingen www.pneumatrol.com Pneumatrol (voorheen RGS Davis) is een gespecialiseerde fabrikant die ISO 9001 gecertificeerd is. Opererend vanuit
Nadere informatieBetrouwbaar, Technisch, Vriendelijk
Betrouwbaar, Technisch, Vriendelijk Stofexplosiegevaar Thema avond PREBES Aquafin Harelbeke 08/06/2017 G. Cailliau, sectormanager BTV West Vlaanderen Inhoud Wanneer is er explosiegevaar? Wettelijk kader.
Nadere informatieEXPLOSIEVEILIGHEIDSDOCUMENT Beoordeling van explosiegevaren door stof van installaties en arbeidsplaatsen
Installatie: Arbeidsplaats: Beschrijving van de installatie en arbeidsplaats Verantwoordelijke: (1) Brandbare Stoffen (2) Gegevens van de meest kritische stof Ontstekingstemperatuur: Ontstekingsenergie:
Nadere informatieIntrinsiek veilige temperatuursensoren volgens ATEX-Richtlijn 94/9/EG. 45 jaar passie en kwaliteit. Gecertificeerde productielocaties
Intrinsiek veilige temperatuursensoren volgens ATEX-Richtlijn 94/9/EG 45 jaar passie en kwaliteit Gecertificeerde productielocaties Sinds de oprichting in 1968 staat de naam Günther voor vooruitstrevende
Nadere informatieBliksem- en overspanningsbeveiliging in industriële installaties
Bliksem- en overspanningsbeveiliging in industriële installaties John van Leeuwen Industry Manager Process 20 mei 2014 Safety@work Den Bosch Page 1 Bliksemschade met 40% toegenomen (bron: NU.NL 6 juli
Nadere informatieExplosieveilige Ribbenbuiskachels Type ERB (RVS)
Explosieveilige Ribbenbuiskachels Type ERB (RVS) Explosieveilige Ribbenbuiskachels typ ERB zijn ontworpen om ruimten te verwarmen waar explosiegevaar kan ontstaan door gebruik van brandbare gassen, dampen
Nadere informatieExplosieveilige Ribbenbuiskachels Type ERB (RVS)
Explosieveilige Ribbenbuiskachels Type ERB (RVS) Sinus Jevi explosieveilige Ribbenbuiskachels worden veelal toegepast in vochtige ruimten en plaatsen waar enige robuustheid vereist is. De kachels zijn
Nadere informatieMagneetveld-sensor voor pneumatische cilinders BIM-IKT-Y1X-H1141
ATEX categorie II 2 G, Ex zone 1 ATEX categorie II 1 D, Ex zone 20 SIL2 volgens IEC 61508 rechthoekig, hoogte 28 mm metaal, GD-Zn magneet-inductieve sensor DC 2-draads, nom. 8,2 VDC uitgang volgens DIN
Nadere informatieGebruiksaanwijzing Schakelversterker N00..A N05..A 80009130 / 00 02 / 2014
Gebruiksaanwijzing Schakelversterker N00..A N05..A 80009130 / 00 0 / 014 Aanwijzingen voor een veilig gebruik in explosiegevaarlijke bereiken 1 Gebruik Apparaten die stroomkringen met intrinsieke veiligheid
Nadere informatieOnline-datasheet FLOWSIC500 GASMETER
Online-datasheet FLOWSI500 FLOWSI500 A B E F US Bestelinformatie Type FLOWSI500 Artikelnr. Op aanvraag e exacte specificaties en prestatiegegevens van het product kunnen afwijken en zijn afhankelijk van
Nadere informatieIO-Link : de industriële communicatiestandaard. IO-Link Group Belgium stelt voor
IO-Link : de industriële communicatiestandaard IO-Link Group Belgium stelt voor Trends in production & automation Industry 4.0 digitizes the entire industrial value chain R&D Supplier Procurement Production
Nadere informatie